1-244
A
<.
550-UH User’s Manual
Embedded fieldbus
The A
<.
550 supports the following Modbus function codes for coils:
1xxxx Mapping – Modbus Discrete Inputs.
The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
•
Bit-wise map of the
STATUS
WORD
(selected using parameter 5305
EFB
CTRL
PROFILE
). The first 32 inputs are reserved for this purpose.
•
Discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
Function Code
Description
01
Read coil status
05
Force single coil
15 (0x0F Hex)
Force multiple coils
Modbus
Ref.
Internal Location
(All Profiles)
ABB
DRV
(5305 = 0 or 2)
DCU
PROFILE
(5305 = 1)
1
0001
STATUS
WORD
– Bit 0
RDY_ON
READY
1
0002
STATUS
WORD
– Bit 1
RDY_RUN
ENABLED
1
0003
STATUS
WORD
– Bit 2
RDY_REF
STARTED
1
0004
STATUS
WORD
– Bit 3
TRIPPED
RUNNING
1
0005
STATUS
WORD
– Bit 4
OFF_2_STA*
ZERO_SPEED
1
0006
STATUS
WORD
– Bit 5
OFF_3_STA*
ACCELERATE
1
0007
STATUS
WORD
– Bit 6
SWC_ON_INHIB
DECELERATE
1
0008
STATUS
WORD
– Bit 7
ALARM
AT_SETPOINT
1
0009
STATUS
WORD
– Bit 8
AT_SETPOINT
LIMIT
1
0010
STATUS
WORD
– Bit 9
REMOTE
SUPERVISION
1
0011
STATUS
WORD
– Bit 10
ABOVE_LIMIT
REV_REF
1
0012
STATUS
WORD
– Bit 11
EXT2
REV_ACT
1
0013
STATUS
WORD
– Bit 12
RUN_ENABLE
PANEL_LOCAL
1
0014
STATUS
WORD
– Bit 13
N/A
FIELDBUS_LOCAL
1
0015
STATUS
WORD
– Bit 14
N/A
EXT2_ACT
1
0016
STATUS
WORD
– Bit 15
N/A
FAULT
1
0017
STATUS
WORD
– Bit 16
Reserved
ALARM
1
0018
STATUS
WORD
– Bit 17
Reserved
REQ_MAINT
1
0019
STATUS
WORD
– Bit 18
Reserved
DIRLOCK
1
0020
STATUS
WORD
– Bit 19
Reserved
LOCALLOCK
1
0021
STATUS
WORD
– Bit 20
Reserved
CTL_MODE
1
0022
STATUS
WORD
– Bit 21
Reserved
Reserved
1
0023
STATUS
WORD
– Bit 22
Reserved
Reserved
1
0024
STATUS
WORD
– Bit 23
Reserved
Reserved
1
0025
STATUS
WORD
– Bit 24
Reserved
Reserved
1
0026
STATUS
WORD
– Bit 25
Reserved
Reserved
1
0027
STATUS
WORD
– Bit 26
Reserved
REQ_CTL
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...