![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 206](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352206.webp)
1-206
A
<.
550-UH User’s Manual
Embedded fieldbus
1. Reset by pressing UP & DOWN arrows simultaneously in edit mode. Save change by pressing
ENTER.
5309
(5009)
DV STATUS
IDLE
1. No network
connection
2. Blown EIA-485
transceiver
3. Wrong application
number (FLN only)
1. Land communication wires as shown in
drawings on page
. Check Repeater
(if installed onsite).
2. See Corrective Action 8. Parameter
Number 5308.
3. Change application number in the
Siemens field panel.
5316
(5016)
DV
PAR 16
(BACnet
Only)
Not
Increasing
Numeric
Value
1. Drive device
address parameter
5302 is set to 128 or
greater.
2. Max Masters is set
too low on all drives.
1. Change parameter 5302 to a unique value
below 128.
2. Change Max Masters property at all
devices on bus to 127.
5306
(5006)
DV
OK MSG
OK
Message
Counter not
increasing
1
1. Master/Client not
communicating with
drive.
2. Failed router
1. Add device and points to the building
control system.
2. Replace router.
Parameter
Number
Display on
Panel
(Symptom)
Possible Cause
Corrective Action
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...