550-UH User’s Manual
1-135
Parameters
Group 32: SUPERVISION
This group defines supervision for up to three signals from
. Supervision monitors a specified parameter and energizes a relay output if
the parameter passes a defined limit. Use
to define the
relay and whether the relay activates when the signal is too low or too high.
Group 32: Supervision
Code Description Range
Resolution
Default
S
3201
SUPERV 1 PARAM
100…178
1
103 (
OUTPUT
FREQ
)
Selects the first supervised parameter.
• Must be a parameter number from
• 100 =
NOT
SELECTED
– No parameter selected.
• 101…178 – Selects parameter 0101…0178.
• If the supervised parameter passes a limit, a relay output is energized.
• The supervision limits are defined in this group.
• The relay outputs are defined in
(definition also specifies which supervision limit is
monitored).
LO
≤
HI
Operating data supervision using relay outputs, when
LO
≤
HI.
• Case A = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
.
Use for monitoring when/if the supervised signal exceeds
a given limit. The relay remains active until the supervised
value drops below the low limit.
• Case B = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
.
Use for monitoring when/if the supervised signal falls
below a given limit. The relay remains active until the
supervised value rises above the high limit.
Note:
Case LO
≤
HI represents a normal hysteresis.
LO
>
HI
Operating data supervision using relay outputs, when
LO>HI.
The lowest limit (
HI
3203) is active initially and remains
active until the supervised parameter goes above the
highest limit (
LO
3202), making that limit the active limit.
That limit remains active until the supervised parameter
goes below the lowest limit (
HI
3203), making that limit
active.
• Case A = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
OVER
or
SUPRV
2
OVER
. Initially the relay is de-energized. It is energized
whenever the supervised parameter goes above the
active limit.
• Case B = Parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2, etc.) value is
SUPRV
1
UNDER
or
SUPRV
2
UNDER
. Initially the relay is energized. It is de-energized whenever the supervised parameter goes below the active
limit.
Note:
Case LO>HI represents a special hysteresis with two separate supervision limits.
3202
SUPERV 1 LIM LO
Depends on selection
-
60.0 Hz
Sets the low limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
3203
SUPERV 1 LIM HI
Depends on selection
-
60.0 Hz
Sets the high limit for the first supervised parameter. See 3201
SUPERV
1
PARAM
above.
Value of supervised parameter
Case A
0
Energized (1)
0
HI
(3203)
LO
(3202)
Case B
Energized (1)
t
t
t
LO
(3202)
HI
(3203)
Value of supervised parameter
Case A
0
Energized (1)
0
Case B
Energized (1)
Active limit
t
t
t
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...