![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 168](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352168.webp)
1-168
A
<.
550-UH User’s Manual
Parameters
5309
EFB STATUS
0…7
1
0 (
IDLE
)
Contains the status of the EFB protocol.
0 =
IDLE
– EFB protocol is configured, but not receiving any messages.
1 =
EXECUT
INIT
– EFB protocol is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the network master and the EFB protocol.
3 =
CONFIG
ERROR
– EFB protocol has a configuration error.
4 =
OFF
-
LINE
– EFB protocol is receiving messages that are NOT addressed to this drive.
5 =
ON
-
LINE
– EFB protocol is receiving messages that are addressed to this drive.
6 =
RESET
– EFB protocol is performing a hardware reset.
7 =
LISTEN
ONLY
– EFB protocol is in listen-only mode.
5310
EFB PAR 10
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40005.
5311
EFB PAR 11
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40006.
5312
EFB PAR 12
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40007.
5313
EFB PAR 13
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40008.
5314
EFB PAR 14
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40009.
5315
EFB PAR 15
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40010.
5316
EFB PAR 16
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40011.
5317
EFB PAR 17
0…65535
1
0
Specifies the parameter mapped to Modbus Register 40012.
5318
EFB PAR 18
0…65535
1
0
For Modbus: Sets additional delay in milliseconds before the A
<.
550 begins transmitting response to the master
request.
5319
EFB PAR 19
0000…FFFF hex
1
0000 hex
ABB Drives profile (
ABB
DRV
LIM
or
ABB
DRV
FULL
) Control Word. Read only copy of the Fieldbus Control Word.
5320
EFB PAR 20
0000…FFFF hex
1
0000 hex
ABB Drives profile (
ABB
DRV
LIM
or
ABB
DRV
FULL
) Status Word. Read only copy of the Fieldbus Status Word.
Group 53: EFB Protocol
Code Description Range
Resolution
Default
S
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...