1-128
A
<.
550-UH User’s Manual
Parameters
Group 29: MAINTENANCE TRIG
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Group 29: Maintenance Trig
Code Description Range
Resolution
Default
S
2901
COOLING FAN TRIG
0.0…6553.5 kh
0.1 kh
0.0 kh
0.0 disables
Sets the trigger point for the drive’s cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902
COOLING FAN ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
Defines the actual value of the drive’s cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2903
REVOLUTION TRIG
0…65535 Mrev
1 Mrev
0 Mrev
0 disables
Sets the trigger point for the motor’s accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904
REVOLUTION ACT
0…65535 Mrev
1 Mrev
0 Mrev
Defines the actual value of the motor’s accumulated revolutions counter.
• When parameter 2903 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 – Resets the parameter.
2905
RUN TIME TRIG
0.0…6553.5 kh
0.1 kh
0.0 kh
0.0 disables
Sets the trigger point for the drive’s run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906
RUN TIME ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
Defines the actual value of the drive’s run time counter.
• When parameter 2905 has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2907
USER MWh TRIG
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
0.0 disables
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
• Value is compared to parameter 2908 value.
0.0 – Disables the trigger.
2908
USER MWh ACT
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
• When parameter 2907
has been set to a non-zero value, the counter starts.
• When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...