![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352076.webp)
1-76
A
<.
550-UH User’s Manual
Parameters
4018
ACT
1
MINIMUM
-1000…1000%
1%
0%
4019
ACT
1
MAXIMUM
-1000…1000%
1%
100%
4020
ACT
2
MINIMUM
-1000…1000%
1%
0%
4021
ACT
2
MAXIMUM
-1000…1000%
1%
100%
4022
SLEEP
SELECTION
-6…7
1
0 (
NOT
SEL
)
4023
PID
SLEEP
LEVEL
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
4024
PID
SLEEP
DELAY
0.0…3600.0 s
0.1 s
60.0 s
4025
WAKE
-
UP
DEV
Depends on Units and Scale
-
0.0%
4026
WAKE
-
UP
DELAY
0.00…60.00 s
0.01 s
0.50 s
4027
PID
1
PARAM
s
ET
-6…14
1
0 (
SET
1)
Group 41: PROCESS PID SET 2
4101
GAIN
0.1…100.0
0.1
2.5
4102
INTEGRATION
TIME
0.0…3600.0 s
0.1 s
3.0 s
4103
DERIVATION
TIME
0.0…10.0 s
0.1 s
0.0 s
4104
PID
DERIV
FILTER
0.0…10.0 s
0.1 s
1.0 s
4105
ERROR
VALUE
INV
0, 1
1
0 (
NO
)
4106
UNITS
0…127
1
4 (%)
4107
UNIT
SCALE
0…4
1
1
4108
0%
VALUE
Depends on Units and Scale
-
0.0%
4109
100%
VALUE
Depends on Units and Scale
-
100.0%
4110
SET
POINT
SEL
0…2, 8…17, 19…20
1
0 (
KEYPAD
)
4111
INTERNAL
SETPNT
Depends on Units and Scale
-
40.0%
4112
SETPOINT
MIN
-500.0…500.0%
0.1%
0.0%
4113
SETPOINT
MAX
-500.0…500.0%
0.1%
100.0%
4114
FBK
SEL
1…13
1
1 (
ACT
1)
4115
FBK
MULTIPLIER
-32.768…32.767
0.001
0.000 (
NOT SEL
)
4116
ACT
1
INPUT
1…7
1
2 (
AI
2)
4117
ACT
2
INPUT
1…7
1
2 (
AI
2)
4118
ACT
1
MINIMUM
-1000…1000%
1%
0%
4119
ACT
1
MAXIMUM
-1000…1000%
1%
100%
4120
ACT
2
MINIMUM
-1000…1000%
1%
0%
4121
ACT
2
MAXIMUM
-1000…1000%
1%
100%
4122
SLEEP
SELECTION
-6…7
1
0 (
NOT
SEL
)
4123
PID
SLEEP
LEVEL
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
4124
PID
SLEEP
DELAY
0.0…3600.0 s
0.1 s
60.0 s
4125
WAKE
-
UP
DEV
Depends on Units and Scale
-
0.0%
4126
WAKE
-
UP
DELAY
0.00…60.00 s
0.01 s
0.50 s
Group 42: EXT / TRIM PID
4201
GAIN
0.1…100.0
0.1
2.5
4202
INTEGRATION
TIME
0.0…3600.0 s
0.1 s
3.0 s
4203
DERIVATION
TIME
0.0…10.0 s
0.1 s
0.0 s
4204
PID
DERIV
FILTER
0.0…10.0 s
0.1 s
1.0 s
4205
ERROR
VALUE
INV
0, 1
1
0 (
NO
)
4206
UNITS
0…127
1
4 (%)
4207
UNIT
SCALE
0…4
1
1
Code
Name
Range
Resolution
Default
User
S
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...