1-42
A
<.
550-UH User’s Manual
Control panel
•
Download User Set 1
- Copies
USER
S
1 parameters (user sets are saved using
parameter 9902
APPLIC
MACRO
) from the Control Panel to the drive.
•
Download User Set 2
- Copies
USER
S
2 parameters from the Control Panel to the
drive.
Handling inexact downloads
In some situations, an exact copy of the download is not appropriate for the target
drive. Some examples:
•
A download to an old drive specifies parameters/values that are not available on
the old drive.
•
A download (from an old drive) to a new drive does not have definitions for the
new parameters – parameters that did not originally exist.
•
A download can include an illegal value for the target drive, e.g. a backup from a
small drive can have a switching frequency of 12 kHz whereas a big drive can
only handle 8k Hz.
As a default, the control panel handles these situations by:
•
Discarding parameters/values not available on
the target drive.
•
Using parameter default values when the
download provides no values or invalid values.
•
Providing a Differences List – A listing of the
type and number of items that the target cannot
accept exactly as specified.
You can either accept the default edits by pressing
READY, or view and edit each item as follows:
1. Highlight an item type in the Differences List (left screen below) and press SEL to
see the details for the selected type (right screen below).
5
The text “Parameter download
successful” is displayed and the
control panel returns to PAR BACKUP
menu. Select EXIT to return to the
main menu.
LOC
DIFFERENCES
----
VALUES UNDER MIN
VALUES OVER MAX
INVALID VALUES
EXTRA PARS
MISSING VALUES
READY
SEL
3
2
1
5
7
LOC
DIFFERENCES
----
VALUES UNDER MIN
VALUES OVER MAX
INVALID VALUES
EXTRA PARS
MISSING VALUES
READY
SEL
3
2
1
5
7
LOC
INVALID VAL
9902 APLIC MACRO
2606*SWITCHING FREQ
12 kHz
8 kHz
3401*DISP 1 SEL
EXIT
EDIT
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...