Group 17: OVERRIDE
This group defines the source for the override activation signal, the override speed/
frequency and pass code and how the override is enabled and disabled.
When override DI is activated, the drive stops and then accelerates to the preset
speed or frequency. When the DI is deactivated the drive stops and reboots. If the
start command, run enable and start enables are active in the AUTO mode the drive
starts automatically and continues normally after override mode. In the HAND mode
the drive returns to OFF mode.
When override is active:
•
Drive runs at preset speed
•
Drive ignores all keypad commands
•
Drive ignores all commands from communication links
•
Drive ignores all digital inputs except override activation/deactivation, RUN
ENABLE and START ENABLE
•
Drive displays alarm message “2020
OVERRIDE
MODE
”
The following faults are ignored:
3
DEVICE OVERTEMP
5
OVERLOAD
6
DC UNDERVOLT
7
AI1 LOSS
8
AI2 LOSS
9
MOTOR TEMP
10
PANEL LOSS
12
MOTOR STALL
14
EXTERNAL FLT 1
15
EXTERNAL FLT 2
17
UNDERLOAD
18
THERM FAIL
21
CURR MEAS
22
SUPPLY PHASE
24
OVERSPEED
28
SERIAL 1 ERR
29
EFB CONFIG FILE
30
FORCE TRIP
31
EFB 1
32
EFB 2
33
EFB 3
34
MOTOR PHASE
1001
PAR PFA REFNEG
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...