![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 178](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352178.webp)
1-178
A
<.
550-UH User’s Manual
Parameters
8120
INTERLOCKS
0…6
1
4 (
DI
4)
Defines operation of the Interlock function. When the Interlock function is enabled:
• An interlock is active when its command signal is absent.
• An interlock is inactive when its command signal is present.
• The A
YK
550 will not start if a start command occurs when the speed regulated motor’s interlock is active – the
control panel displays an alarm (2015,
PFA
I
LOCK
).
Wire each Interlock circuit as follows:
• Wire a contact of the motor’s On/Off switch to the Interlock circuit – the drive’s PFA logic can then recognize that
the motor is switched off and start the next available motor.
• Wire a contact of the motor thermal relay (or other protective device in the motor circuit) to the Interlock input – the
drive’s PFA logic can then recognize that a motor fault is activated and stop the motor.
0 =
NOT
SEL
– Disables the Interlock function. All digital inputs are available for other purposes.
• Requires 8118
AUTOCHNG
INTERV
= 0.0 (The Autochange function must be disabled if Interlock function is
disabled.)
1 =
DI
1 – Enables the Interlock function and assigns a digital input (starting with
DI
1) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFA
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0.0, and otherwise enabled).
Group 81: PFA Control
Code Description Range
Resolution
Default
S
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1: Speed Reg Motor
DI
2…
DI
6: Free
Not allowed
1
DI
1: Speed Reg Motor
DI
2: First PFA Relay
DI
3…
DI
6: Free
DI
1: First PFA Relay
DI
2…
DI
6: Free
2
DI
1: Speed Reg Motor
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4…
DI
6: Free
DI
1: First PFA Relay
DI
2: Second PFA Relay
DI
3…
DI
6: Free
3
DI
1: Speed Reg Motor
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5…
DI
6: Free
DI
1: First PFA Relay
DI
2: Second PFA Relay
DI
3: Third PFA Relay
DI
4…
DI
6: Free
4
DI
1: Speed Reg Motor
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5: Fourth PFA Relay
DI
6: Free
DI
1: First PFA Relay
DI
2: Second PFA Relay
DI
3: Third PFA Relay
DI
4: Fourth PFA Relay
DI
5…
DI
6: Free
5
DI
1: Speed Reg Motor
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5: Fourth PFA Relay
DI
6: Fifth PFA Relay
DI
1: First PFA Relay
DI
2: Second PFA Relay
DI
3: Third PFA Relay
DI
4: Fourth PFA Relay
DI
5: Fifth PFA Relay
DI
6: Free
6
Not allowed
DI
1: First PFA Relay
DI
2: Second PFA Relay
DI
3: Third PFA Relay
DI
4: Fourth PFA Relay
DI
5: Fifth PFA Relay
DI
6: Sixth PFA Relay
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...