1-124
A
<.
550-UH User’s Manual
Parameters
2304
ACC COMPENSATION
0.00…600.00 s
0.01 s
0.00 s
Sets the derivation time for acceleration compensation.
• Adding a derivative of the reference to the output of the speed controller compensates for inertia during
acceleration.
• 2303
DERIVATION
TIME
describes the principle of derivative action.
• Rule of thumb: Set this parameter between 50 and 100% of the sum of the mechanical time constants for the
motor and the driven machine.
• The figure shows the speed responses when a high inertia load is accelerated along a ramp.
*Note:
You can use parameter 2305
AUTOTUNE
RUN
to automatically set acceleration compensation.
2305
AUTOTUNE RUN
0, 1
1
0 (
OFF
)
Starts automatic tuning of the speed controller.
0 =
OFF
– Disables the Autotune creation process. (Does not disable the operation of Autotune settings.)
1 =
ON
– Activates speed controller autotuning. Automatically reverts to
OFF
.
Procedure:
Note:
The motor load must be connected.
• Run the motor at a constant speed of 20 to 40% of the rated speed.
• Change the autotuning parameter 2305 to
ON
.
The drive:
• Accelerates the motor.
• Calculates values for proportional gain, integration time and acceleration compensation.
• Changes parameters 2301, 2302 and 2304 to these values.
• Resets 2305 to
OFF
.
Group 23: Speed Control
Code Description Range
Resolution
Default
S
Speed reference
Actual speed
*
No acceleration compensation
Acceleration compensation
%
%
t
t
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...