ABB i-bus® KNX
PARAMETERS
7.4.93
Sending and switching delay after bus voltage recovery
This parameter is used to define the sending and switching delay after bus voltage recovery.
More information: →
Sending and switching delay, Page 185
.
Note
After bus voltage recovery, the device waits for the sending delay time to elapse before sending tele-
grams on the bus.
Option
2 ... 255 s
Prerequisites for visibility
• The parameter is in the parameter window
.
7.4.94
Sending cycle
This parameter is used to define the cycle in which the group object
Option
00:00:01 … 00:10:00 … 18:12:15 hh:mm:ss
Prerequisites for visibility
Enable group object "In operation"
\ Option
Yes
• The parameter is in the parameter window
.
7.4.95
Setpoint for frost protection (building protection, heating)
This parameter is used to define the setpoint temperature that must not be fallen below in the
Building
Protection heating operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be lower than the value in the parameter
.
If the device is in the
Heating operating mode, the setpoint is active in the following cases:
• Controller receives the status "Window open"
• The controller is deactivated via group object
• Controller is placed in the
Building Protection
operating mode via group objects
Operating mode override (master)
Option
5 … 7 … 15 °C
Prerequisites for visibility
\ Option
Controller channel
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
111