ABB i-bus® KNX
MOUNTING AND INSTALLATION
5
Mounting and installation
5.1
Information about mounting
DANGER
‒
Severe injuries due to touch voltage
Feedback from differing phase conductors can produce touch voltages and lead to severe injuries.
▶ Operate the device only in a closed housing (distribution board).
▶ Disconnect all phases before working on the electrical connection.
The device can be mounted in any position as required on a 35 mm mounting rail.
The electrical connection to the loads is made using screw terminals. The connection to the bus
(ABB i-bus® KNX) is made using the bus connection terminal supplied. The terminal assignment is lo-
cated on the housing.
Note
The maximum permissible current consumption on a KNX line must not be exceeded.
▶ During planning and installation, ensure that the KNX line is correctly dimensioned. The device has a
maximum current consumption of 12 mA.
5.2
Mounting on mounting rail
Note
No additional tools are required for mounting on a mounting rail.
2CDC072013F0015
Fig. 7: Mounting on mounting rail
1. Place the mounting rail holder on the upper edge of the mounting rail and push down.
2. Push the lower part of the device toward the mounting rail until the mounting rail holder engages.
ð
The device is now mounted on the mounting rail.
3. Relieve the pressure on the top of the housing.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
29