ABB i-bus® KNX
PARAMETERS
7.4.85
Open if control value greater than or equal to
This parameter is used to define the control value as of which an On signal is sent to the valve drive. If
the control value is less than the value set here, an Off signal is sent.
Option
1 … 100 %
Prerequisites for visibility
\ Parameter
\ Option
Open/close signal
• The parameter is in the parameter window
7.4.86
Valve drive opening/closing time
This parameter is used to set the time the valve drive requires to open the valve completely (from posi-
tion 0 % to position 100 %) or close it completely.
Note
The time is listed in the technical data for the valve drive and corresponds to the total run time.
Option
10 … 180 … 900 s
Prerequisites for visibility
\ Parameter
\ Options
Thermoelectric (PWM)
/
Open/close signal
• The parameter is in the parameter window
7.4.87
Setpoint temperature offset when summer compensation ends
This parameter is used to define the setpoint temperature offset when summer compensation ends.
More information: →
Summer compensation, Page 187
.
Option
0.0 … 6.0… 12.7 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
\ Parameter
\ Option
Yes
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
104