ABB i-bus® KNX
GROUP OBJECTS
8.3
Group objects, Channel x - General
Function
Group object name
Data point
type
Length
Flags
Forced operation, 2-bit
Channel X – General
DPT 2.001
2 bit
C
W
This group object is used to activate/deactivate 2-bit forced operation via the bus (ABB i-bus® KNX),
Forced operation is activated/deactivated with bit 1. Bit 0 is used to toggle between the states
Forced operation active "ON"
and
Forced operation active "OFF"
.
If forced operation is active, the control value cannot be controlled via KNX commands.
Telegram value (bit 1 | bit 0):
•
0 | 0 = Forced operation inactive
•
0 | 1 = Forced operation inactive
•
1 | 0 = Forced operation active "OFF"
•
1 | 1 = Forced operation active "ON"
Prerequisites for visibility
•
\ Option
Activated 2 bit
Forced operation, 1-bit
Channel X – General
DPT 1.002
1 bit
C
W
This group object is used to activate/deactivate 1-bit forced operation via the bus (ABB i-bus® KNX).
If forced operation is active, the control value cannot be controlled via KNX commands.
Telegram value:
•
Depends on the setting in the parameter
Prerequisites for visibility
•
\ Option
Activated 1 bit – 0 active
/
Activated 1 bit – 1
active
Error "Heating/cooling changeover"
receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the following group objects on the bus (ABB i-bus® KNX):
•
•
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
\ Option
Via group object
/
Via group
object or via slave
•
–
Option
Activated
–
Monitor receipt of group object "Heating/cooling changeover"
Option
Activated
Error "Window contact" receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the group object Window contact on the bus (ABB i-bus® KNX).
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
–
Option
Controller channel
–
\
Option
Via group object
•
–
Option
Activated
–
Monitor receipt of group object "Window contact"
\
Option
Activated
Error "Dew point alarm" receipt
Channel X – General
DPT 1.005
1 bit
C R
T
The group object sends the error status for the cyclical monitoring of the group object Dew point alarm [input x] on the bus (ABB i-bus® KNX).
The monitoring cycle is set in the parameter
Time interval for cyclical monitoring
.
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
all options except
Deactivated
–
Option
Via group object
•
–
Option
Activated
–
Monitor receipt of group object "Dew point alarm"
\
Option
Activated
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
152
Note about navigation in the PDF: Key combination 'Alt + left arrow'