ABB i-bus® KNX
GROUP OBJECTS
Function
Group object name
Data point
type
Length
Flags
Status Control value additional-
stage heating
Channel X – Controller
DPT 1.001
1 bit
C R
T
This group object sends the control value for additional-stage heating on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
and the associated control type. A control type is preset depending on
the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-bit value (DPT 1.001) for the following control types:
•
2-point 1 bit (On/Off)
•
PI PWM (On/Off)
Telegram value:
•
1 = On
•
0 = Off
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
–
Option
Free configuration
Status Control value basic-stage cooling
Channel X – Controller
DPT 5.001
1 byte
C R
T
This group object sends the control value for basic-stage cooling on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
Basic-stage cooling [controller]
and the associated control type. A control type is preset
depending on the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-byte value (DPT 5.001) with the following control types:
•
2-point 1 byte (0/100 %)
•
PI continuous (0 … 100 %)
•
PI continuous (0 … 100 %) for fan coil
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (e.g. 0x0001) or by changing to a different DPT (e.g. DPT 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
Options
Area cooling (e.g. cooling ceiling) / Free configuration
Status Control value basic-stage cooling
Channel X – Controller
DPT 1.001
1 bit
C R
T
This group object sends the control value for basic-stage cooling on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
Basic-stage cooling [controller]
and the associated control type. A control type is preset
depending on the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-bit value (DPT 1.001) for the following control types:
•
2-point 1 bit (On/Off)
•
PI PWM (On/Off)
Telegram value:
•
1 = On
•
0 = Off
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
Option
Free configuration
Status Control value additional-
stage cooling
Channel X – Controller
DPT 5.001
1 byte
C R
T
This group object sends the control value for additional-stage cooling on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
and the associated control type. A control type is preset depending on
the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-byte value (DPT 5.001) with the following control types:
•
2-point 1 byte (0/100 %)
•
PI continuous (0 … 100 %)
•
PI continuous (0 … 100 %) for fan coil
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (e.g. 0x0001) or by changing to a different DPT (e.g. DPT 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
all options except
Deactivated
–
\
Options
Area cooling (e.g. cooling ceiling) / Free configuration
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
158