Standard function blocks
266
FIO_11_AO_slot1
(10090)
Illustration
Execution time
4.9 µs
Operation
The block controls the analogue output (AO1) of a FIO-11 Analog I/O Extension
mounted on slot 1 of the drive control unit.
The block converts the input signal (AO scaled) to a 0…20 mA signal (AO) that drives
the analogue output; the input range AO Min Scale … AO Max Scale corresponds to
the current signal range of AO Min … AO Max.
AO Min Scale must be smaller than AO Max Scale; AO Max can be greater or smaller
than AO Min.
FIO_11_AO_slot1
53
TLA1 1 msec
(1)
AO Min
AO Max
AO Min Scale
AO Max Scale
AO scaled
AO
AO(53)
Error
Error(53)
AO [mA]
0
20
AO scaled
32768
-32768
0
AO M
ax
Sc
al
e
AO M
in Scal
e
AO Max
AO Min
AO Min < AO Max