292 Fieldbus control with the embedded fieldbus
Enables fault reset through
bit 4 (with ABB drives profile
bit 7).
40001 bit 7 40031 bit 4
Local control mode lock signal
through
bit 14
-
40031 bit
14
Saves parameter value changes
(including those made through
fieldbus control) to permanent
memory.
41607
Inverted Start enable 1 (Start
disable) through
bit 18
-
40032 bit
18
Inverted Start enable 2 (Start
disable) through
bit 19
-
40032 bit
19
LIMITS
ABB DRV
DCU
Acceleration/deceleration ramp
pair selection through
bit 10
-
40031 bit
10
Ramp input to zero through
bit 13 (with ABB
drives profile
bit
6)
40001 bit 6 40031 bit
13
COMMUNICATION FAULT FUNCTIONS
ABB DRV
DCU
Determines drive action in case
fieldbus communication is lost.
43018
0.1…60.0 s Defines the time between
communication loss detection and
the action selected with parameter
.
43019
PID CONTROLLER REFERENCE SIGNAL SOURCE SELECTION
ABB DRV
DCU
PID control reference (REF2)
40003 for REF2
Parameter
Setting for
fieldbus
control
Function/Information
Modbus register
address