200 Actual signals and parameters
2007 MINIMUM
FREQ
Defines the minimum limit for the drive output frequency.
A positive (or zero) minimum frequency value defines two
ranges, one positive and one negative.
A negative minimum frequency value defines one speed
range.
Note:
.
0.0 Hz
-500.0…500.0 Hz Minimum frequency
1 = 0.1 Hz
2008 MAXIMUM
FREQ
Defines the maximum limit for the drive output frequency.
E: 50.0 Hz
U: 60.0 Hz
0.0…500.0 Hz
Maximum frequency
1 = 0.1 Hz
21 START/STOP
Start and stop modes of the motor
2101 START
FUNCTION
Selects the motor starting method.
AUTO
The drive starts the motor instantly from zero frequency. If
flying start is required, use selection
1
DC MAGN
The drive pre-magnetizes the motor with DC current before
the start. The pre-magnetizing time is defined by parameter
Note:
Starting the drive connected to a rotating motor is not
possible when
is selected.
WARNING!
The drive starts after the set pre-
magnetizing time has passed even if the motor
magnetization is not completed. In applications where a full
break-away torque is essential, always ensure that the
constant magnetizing time is long enough to allow
generation of full magnetization and torque.
2
All parameters
No.
Name/Value
Description
Def/FbEq
0
f
value is < 0
value is > 0
f
0
-(
)
-(
)
t
t
Allowed
frequency range
Allowed
frequency range
Allowed
frequency range