Technical data 351
Ambient conditions
Environmental limits for the drive are given below. The drive is to be
used in a heated indoor controlled environment.
Operation
installed for
stationary use
Storage
in the protective
package
Transportation
in the protective
package
Installation site altitude
0 to 2000 m (6600 ft)
above sea level
(above 1000 m
[3300 ft], see section
on page
-
-
Air temperature
-10 to +50 °C (14 to
122 °F).
No frost
allowed. See section
on page
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
0 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is
60% in the presence of corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
According to
IEC 60721-3-3,
chemical gases:
Class 3C2
solid particles: Class
3S2.
Note:
The drive must
be installed in clean
air according to
enclosure
classification.
Note:
Cooling air
must be clean, free
from corrosive
materials and
electrically conductive
dust.
According to
IEC 60721-3-1,
chemical gases:
Class 1C2
solid particles: Class
1S2
According to
IEC 60721-3-2,
chemical gases:
Class 2C2
solid particles: Class
2S2
Sinusoidal vibration
(IEC 60721-3-3)
Tested according to
IEC 60721-3-3,
mechanical
conditions: Class 3M4
2…9 Hz, 3.0 mm
(0.12 in)
9…200 Hz, 10 m/s
2
(33 ft/s
2
)
-
-
Shock
(IEC 60068-2-27,
ISTA 1A)
Not allowed during
operation.
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
), 11 ms.
According to ISTA 1A.
Max. 100 m/s
2
(330 ft/s
2
), 11 ms.
Free fall
Not allowed
76 cm (30 in)
76 cm (30 in)