Actual signals and parameters 183
DI4U,5D(NC)
See parameter
31
FREQ INPUT
See parameter
32
1107 REF2 MIN
Defines the minimum value for external reference REF2.
Corresponds to the minimum setting of the used source
signal.
0.0%
0.0…100.0%
Value in percent of the maximum frequency / maximum
speed / nominal torque. See the example for parameter
for correspondence to the source signal
limits.
1 = 0.1%
1108 REF2 MAX
Defines the maximum value for external reference REF2.
Corresponds to the maximum setting of the used source
signal.
100.0%
0.0…100.0%
Value in percent of the maximum frequency / maximum
speed / nominal torque. See the example for parameter
for correspondence to the source signal
limits.
1 = 0.1%
12 CONSTANT
SPEEDS
Constant speed (drive output frequency) selection and
values. See section
on page
.
1201 CONST
SPEED SEL
Activates the constant speeds (drive output frequencies) or
selects the activation signal.
NOT SEL
No constant speed in use
0
DI1
Speed defined by parameter
is
activated through digital input DI1. 1 = active, 0 = inactive.
1
DI2
Speed defined by parameter
is
activated through digital input DI2. 1 = active, 0 = inactive.
2
DI3
Speed defined by parameter
is
activated through digital input DI3. 1 = active, 0 = inactive.
3
DI4
Speed defined by parameter
is
activated through digital input DI4. 1 = active, 0 = inactive.
4
DI5
Speed defined by parameter
is
activated through digital input DI5. 1 = active, 0 = inactive.
5
DI1,2
Constant speed selection through digital inputs DI1 and
DI2.1 = DI active, 0 = DI inactive.
7
DI2,3
See selection
.
8
DI3,4
See selection
.
9
DI4,5
See selection
.
10
All parameters
No.
Name/Value
Description
Def/FbEq
DI1 DI2 Operation
0
0 No constant speed
1
0 Speed defined by par.
0
1 Speed defined by par.
1
1 Speed defined by par.