Actual signals and parameters 215
3007 MOT LOAD
CURVE
Defines the load curve together with parameters
With the default value 100%, motor overload protection is
functioning when the constant current exceeds 127% of the
value.
The default overloadability is at the same level as what
motor manufacturers typically allow below 30 °C (86 °F)
ambient temperature and below 1000 m (3300 ft) altitude.
When the ambient temperature exceeds 30 °C (86 °F) or
the installation altitude is over 1000 m (3300 ft), decrease
value according to the motor
manufacturer’s recommendation.
Example:
If the constant protection level needs to be 115%
of the nominal motor current, set parameter
value to
91% (= 115/127·100%).
100%
50.…150%
Allowed continuous motor load relative to the nominal motor
current
1 = 1%
3008 ZERO SPEED
LOAD
Defines the load curve together with parameters
and
70%
25.…150%
Allowed continuous motor load at zero speed in percent of
the nominal motor current
1 = 1%
All parameters
No.
Name/Value
Description
Def/FbEq
100 =
127%
150
50
f
Output current relative (%) to