180 Actual signals and parameters
1103 REF1 SELECT Selects the signal source for external reference REF1. See
Block diagram: Reference source for EXT1
on page
KEYPAD
Control panel
0
AI1
Analog input AI1
1
AI2
Analog input AI2
2
AI1/JOYST
Analog input AI1 as joystick. The minimum input signal runs
the motor at the maximum reference in the reverse
direction, the maximum input at the maximum reference in
the forward direction. Minimum and maximum references
and
.
Note:
must be set to
WARNING!
If parameter
is set to
0 V and analog input signal is lost (ie 0 V), the rotation
of the motor is reversed to the maximum reference. Set the
following parameters to activate a fault when analog input
signal is lost:
to 20% (2 V or 4 mA).
to 5% or higher.
.
3
AI2/JOYST
See selection
4
DI3U,4D(R)
Digital input DI3: Reference increase. Digital input DI4:
Reference decrease. Stop command resets the reference to
zero. Parameter
defines the rate of
the reference change.
5
DI3U,4D
Digital input DI3: Reference increase. Digital input DI4:
Reference decrease. The program stores the active speed
reference (not reset by a stop command). When the drive is
restarted, the motor ramps up at the selected acceleration
rate to the stored reference. Parameter
defines the rate of the reference change.
6
COMM
Fieldbus reference REF1
8
COMM+AI1
Summation of fieldbus reference REF1 and analog input AI.
See section
Reference selection and correction
on page
.
9
COMM*AI1
Multiplication of fieldbus reference REF1 and analog input
AI1. See section
Reference selection and correction
on
.
10
All parameters
No.
Name/Value
Description
Def/FbEq
par.
= 20%, par
= 100%
+2
%
-
2%
0
Speed ref
(REF1)
AI1
2 V / 4 mA
10 V / 20 mA
6
Hysteresis 4%
of full scale
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182