178 Actual signals and parameters
COMM
Fieldbus interface as the source for the start and stop
bits
0…1. The Control word is sent by the fieldbus controller
through the embedded fieldbus (Modbus) to the drive. For
the Control word bits, see section
.
10
TIMED FUNC 1 Timed start/stop control. Timed function 1 active = start,
timed function 1 inactive = stop. See parameter group
11
TIMED FUNC 2 See selection
.
12
TIMED FUNC 3 See selection
.
13
TIMED FUNC 4 See selection
.
14
DI5
Start and stop through digital input DI5. 0 = stop, 1 = start.
Direction is fixed according to parameter
(setting
20
DI5,4
Start and stop through digital input DI5. 0 = stop, 1 = start.
Direction through digital input DI4. 0 = forward, 1 = reverse.
To control direction, parameter
must be
21
SUPRV1
OVER
Start when the value of supervision parameter 1 goes over
the supervision high limit. Stop when the value goes below
the low limit. See parameter group
27
SUPRV1
UNDER
Start when the value of the supervision parameter 1 goes
below the supervision low limit. Stop when the value goes
over the high limit. See parameter group
.
28
SUPRV2
OVER
See selection
29
SUPRV2
UNDER
See selection
.
30
SUPRV3
OVER
See selection
.
31
SUPRV3
UNDER
See selection
.
32
S
DI2
Start and stop as for
. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control
direction, parameter
setting must be
33
SUP1
UDR+DI2
Start and stop as for
. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control
direction, parameter
setting must be
34
1002 EXT2
COMMANDS
Defines the connections and the source for the start, stop
and direction commands for external control location 2
(EXT2).
1003 DIRECTION
Enables the control of rotation direction of the motor, or fixes
the direction.
Note:
The Pump cleaning function can override this
FORWARD
Fixed to forward
1
All parameters
No.
Name/Value
Description
Def/FbEq