Actual signals and parameters 179
REVERSE
Fixed to reverse
2
REQUEST
Control of rotation direction allowed
3
1011 PANEL FORCE
STOP
Enables stopping the drive from the control panel even
when not in local control.
DISABLE
Control panel stop button is active only in local control
0
ENABLE
Drive can be stopped from the control panel in remote
control
1
11 REFERENCE
SELECT
Panel reference type, external control location selection and
external reference sources and limits
1101 KEYPAD REF
SEL
Selects the type of the reference in the local control mode.
REF1(Hz/rpm) Frequency reference in Hz
1
REF2(%)
%-reference
2
1102 EXT1/EXT2
SEL
Defines the source from which the drive reads the signal
that selects between the two external control locations,
EXT1 or EXT2.
EXT1
EXT1 active. The control signal sources are defined by
parameters
and
0
DI1
Digital input DI1. 0 = EXT1, 1 = EXT2.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
EXT2
EXT2 active. The control signal sources are defined by
parameters
and
7
COMM
Fieldbus interface as the source for EXT1/EXT2 selection,
ie Control word
bit 5 (with ABB
drives profile
bit 11). The Control word is
sent by the fieldbus controller through the embedded
fieldbus (Modbus) to the drive. For the Control word bits,
on page
ABB drives communication profile
on page
.
8
TIMED FUNC 1 Timed EXT1/EXT2 control selection. Timed function 1 active
= EXT2, timed function 1 inactive = EXT1. See parameter
group
.
9
TIMED FUNC 2 See selection
.
10
TIMED FUNC 3 See selection
.
11
TIMED FUNC 4 See selection
.
12
DI1(INV)
Inverted digital input DI1. 1 = EXT1, 0 = EXT2.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5