Actual signals and parameters 193
COMM
Fieldbus interface as the source for inverted Run enable
signal (Run disable), ie Control word
bit 6 (with ABB drives profile
bit 3). The
Control word is sent by the fieldbus controller through the
embedded fieldbus (Modbus) to the drive. For the Control
and
ABB drives communication profile
on page
7
DI1(INV)
External signal required through inverted digital input DI1. 0
= Run enable. If Run enable signal is switched on, the drive
does not start or coasts to stop if it is running.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
1602 PARAMETER
LOCK
Selects the state of the parameter lock. The lock prevents
parameter changing from the control panel.
LOCKED
Parameter values cannot be changed from the control
panel. The lock can be opened by entering the valid code to
.
The lock does not prevent parameter changes made by
macros or fieldbus.
0
OPEN
The lock is open. Parameter values can be changed.
1
NOT SAVED
Parameter changes from the control panel are not stored
into the permanent memory. To store changed parameter
value to
.
2
1603 PASS CODE
Selects the pass code for the parameter lock (see
).
0
0…65535
Pass code. Setting 358 opens the lock. The value reverts
back to 0 automatically.
1 = 1
1604 FAULT RESET
SEL
Selects the source for the fault reset signal. The signal
resets the drive after a fault trip if the cause of the fault no
longer exists.
KEYPAD
Fault reset only from the control panel
0
DI1
Reset through digital input DI1 (reset on the rising edge of
DI1) or from the control panel
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
START/STOP
Reset along with the stop signal received through a digital
input, or from the control panel.
Note:
• Do not use this option when start, stop and direction
commands are received through fieldbus communication.
• This option does not work with control panel, when
7
All parameters
No.
Name/Value
Description
Def/FbEq
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182