Commissioning
System Manual
│81
6.2.6
IP switch actuator
Address the device via the " IP Touch 7"
1
2
Fig. 56: IP switch actuator: commissioning mode
To address the device, perform the following steps:
1. Boot up the device.
– The device boots up automatically when the power supply is connected.
– If the device is already booted up, briefly interrupt the power supply of the device. The
device reboots.
– The LED LED [1] lights up permanent after the automatic boot up.
2. Activating the "Commissioning mode":
– After the device has booted and the LED [1] lights up permanent, briefly press the
"Reset" [2] button.
– The LED [1] then flashes slowly. The flashing signals that the device is in
"Commissioning mode".
– If no entry is made within the next 5 minutes, the device exits the "Commissioning
mode" automatically.