Alarm Handling 

Alarm definition 

An alarm is individually identified by three values: 

 

Alarm Type  Alarms are classified in three different types 

Camera: 

 all alarms generated at a camera receiver 

Panel: 

alarms generated by contact alarm, or third party serial alarm panels 

Peripheral: 

alarm generated by various types of Meyertech peripheral equipment, e.g. 

Vcr interfaces, remote site interfaces. 

 

Alarm Device The alarm device usually indicates the address of the device generating the alarm, 
depending on the type of the alarm. Device 0 represents all devices of a particular type (i.e. global 
mapping) 

 

Alarm Number The actual number of the alarm circuit on the alarmed device. Number 0 represents 

all alarms on a particular device(i.e. global mapping). 

Alarm Mapping 

 
Alarm Category 

Reporting 
device e.g. 

Type 

Device 

Number 

ZoneVu receiver 
alarms 

ZVR-x30 

Camera 

Camera address 

1 : Tamper alarm 
2 – 7 : Contact i/p s  1 – 6 
8 : Video fail 
9 : Communications fail 

ZoneVu Victa 
alarms 

ZVM-Series2 
 
(

Note:

 RS232 

Plugged into 
any PC Port) 

Camera 

Camera address 

1 : Tamper alarm 
2 – 7 : Contact alarms 1 – 6 on 
receiver reported via matrix 
8: Video Loss 

Matrix Video Loss 

All Matrixes 

Camera 

Matrix input / camera no. 

8 : Video fail 

Panasonic & JVC 
dome alarms 

ZSC-EFD or 
ZVS-MSI-48 

Camera 

Camera address 

1 : all dome alarms 
9 : Communications fail 

Contact alarm rack 

ZVA-032 

Panel 

Alarm card number 

Contact number on card 
255 : Device fail 

Galaxy alarm panel 

ZSC-EFD 

Panel 

1

st

 digit of Zone number 

Remaining digits of zone number 

Teltronic Alarm 

ZSC-EFD 

Panel 

6 – 16 
6 for help points 1 – 100 
7 for 101 – 200 etc 

Help point number without the 
hundreds. 

Surguard (MLR2) 

ZVS-MSI 

Panel 

Account code 

Zone number (or user number)  

Video recorder 

ZVS-MSI-23 

Peripheral 

MAC address of  
ZVS-MSI 

1-3 : Tape Fault channels 1 – 3 
4–6 : Tape end Channels 1 – 3 
7–9 : Hardware fail Channels 1–3 
10-12 : Video loss Channels 1 – 3 
13-15 : Comms fail Channels 1 – 3 
255 : Device fail 

ZVM-328 built in 
contact alarms 

ZVM-328 

Peripheral 

100 

Contact number 1 - 32 

Dial-in alarms 

ZSI-320 

Peripheral 

MAC address of   
ZSI-320 

Site number 
255 : Device fail 

Contact alarm 
inputs 

ZVS-IOM8 

Peripheral 

MAC address of   
ZVS-IOM8 

Input number 
255 : Device fail 

Power fail 

ZVS3-PSU-xD 

Peripheral 

MAC address of   
PSU 

1 : PSU A fail 
2 : PSU B fail 
255 : Device fail 

Matrix 

ZVS3-VRM 

Peripheral 

MAC address of  
ZVS3-VRM + 100 

255 : Device fail 

Keyboard 

ZVK-xxx 

Peripheral 

MAC address of 
keyboard 

255 : Device fail 

Site controller 

ZSC-1000 / 500 

Peripheral 

200 

255 : Device fail 
Site no. indicates which ZSC failed 

Summary of Contents for ZSC-1000 plus

Page 1: ...USER MANUAL USER MANUAL USER MANUAL USER MANUAL ZSC 1000plus CCTV System Controller Issue 18 ZSC 1000plus...

Page 2: ...13 Sequences 13 Timed Events 14 Embedded Firmware Drivers EFD 14 Alarm Handling 15 Configuration 16 Intersite Port 16 PC2 Port 17 ZVK Port 17 ZVK Extra 18 ZVM Port 18 Camera Telemetry 19 PC1 Port 20...

Page 3: ...S KEY FEATURES Local Site Management Intersite communications Alarm handling System backup Third party control interfaces The information in this manual is believed to be accurate and reliable However...

Page 4: ...Port This port is used for communications between sites and control rooms It is very rare that this port has an application for anything other than connection to another site controller ZVR Ports Thes...

Page 5: ...IS DOCUMENT MAY BE REPRODUCED OR DISTRIBUTED IN ANY FORM WITHOUT PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2002 ALL RIGHTS RESERVED 02 12 02 DATE VisioDocument ZoneVu ZVM 328 intersite RS...

Page 6: ...HOUT PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2002 ALL RIGHTS RESERVED 02 12 02 DATE VisioDocument intersite RS422 485 ZVK 77 master ZoneVu Series 2 ZVC 256 ZoneVu RS422 RS232 RS485 VIDE...

Page 7: ...PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2002 ALL RIGHTS RESERVED 02 12 02 DATE VisioDocument RS422 485 ZVK 77 master RS422 RS232 RS485 VIDEO LAN RS422 ZSC 1000 ZoneVu RS422 Victa 1 Loca...

Page 8: ...PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2002 ALL RIGHTS RESERVED 02 12 02 DATE VisioDocument RS422 485 ZVK 77 master RS422 RS232 RS485 VIDEO LAN RS422 ZSC 1000 ZoneVu RS422 Victa 1 Loca...

Page 9: ...PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2002 ALL RIGHTS RESERVED 02 12 02 DATE VisioDocument RS422 485 ZVK 77 master RS422 RS232 RS485 VIDEO LAN RS422 ZSC 1000 ZoneVu RS422 Victa 1 Loca...

Page 10: ...UT PRIOR WRITTEN CONSENT FROM MEYERTECH LIMITED COPYRIGHT 2006 ALL RIGHTS RESERVED 14 08 06 DATE CHKD ZoneVu Series 2 ZVM 9648IXR ZSC 1000 ZoneVu MONITOR ZVK 77 RS422 RS232 RS485 VIDEO LAN VICTA alarm...

Page 11: ...and are managed transparently by the site controllers A trunk is normally fed from an output of the matrix at one site A to an input on the matrix at a second site B This trunk must then be configure...

Page 12: ...A Range of camera numbers usually those that are beyond the range of the local matrix can be used to reference cameras at another site This removes the need for the operator to select a site number an...

Page 13: ...on The normal method of telemetry distribution is through the controller s ZVR ports The Camera Telemetry configuration section can also be used to route telemetry through alternative ports The most c...

Page 14: ...ugh the sequences does not stop them from running Stopping A Sequence A sequence can be stopped by either of 2 methods Select the monitor and then select a camera to display on the monitor This overri...

Page 15: ...8 Video Loss Matrix Video Loss All Matrixes Camera Matrix input camera no 8 Video fail Panasonic JVC dome alarms ZSC EFD or ZVS MSI 48 Camera Camera address 1 all dome alarms 9 Communications fail Con...

Page 16: ...00 57600 and 128000 9600 is recommended for systems of less than 6 site Greater than 6 sites should use 19200 With many active sites i e operators at multiple sites controlling remote cameras 57600 ma...

Page 17: ...ommunications occurs Valid values are 1200 2400 4800 9600 19200 28800 38400 57600 and 128000 Default 9600 Audit Mode Select Audit mode only when Fusion Audit ZVK is connected to this port Default Off...

Page 18: ...r connection to devices on this port May cause problems with some older keyboards Default On ZVM Port MAC address The address to which the unit will respond to polls on this port Default 1 Terminated...

Page 19: ...is address will be polled allows the receiver to return alarm and or status information Default Off Reversed To correct for reversals in individual cameras Where a direction s is reversed tick the app...

Page 20: ...clocks switchers multiplexers and alarm panels Those required must be specified at time of order Default ZoneVu Baud Rate Defines the baud rate at which the PC1 communications occurs Valid values are...

Page 21: ...transmit these commands onto another port For each VCR in the range 1 to 90 Port The port used to transmit VCR commands onto Default Zvk MUX Ports The ZSC 1000 routes commands out to ZVS MSI units co...

Page 22: ...Address is the multiplexer number Monitor Used where an input is connected directly to a monitor i e no matrix This is most commonly used where the input is a trunk line switched at a remote site o O...

Page 23: ...t on ZVK PC1 PC2 ports in Zonevu format Default ZVM Series 2 matrix 0 None matrix 1 19 1 st Input Input number that the matrix starts at Default 1 matrix 0 0 matrix 1 19 1 st Output Output number that...

Page 24: ...ix input A fixed caption is of limited use in this case Parameters are denoted with a sign followed by a number to choose the parameter 1 The matrix input number 2 The matrix output number 3 The camer...

Page 25: ...an be defined Note The last trunk should be followed by a dummy entry with site set to 0 Gaps should not be left in the trunk tables as any dummy or blank entries in the list are treated as the end of...

Page 26: ...ite For each output trunk in the range 0 to 127 the following can be defined Note The last trunk should be followed by a dummy entry with site set to 0 Gaps should not be left in the trunk tables as a...

Page 27: ...if further mappings follow Map Video When enabled all switches for cameras in the range are re mapped Select this if the matrix input does not match the camera number selected by the operator Default...

Page 28: ...only work in the operating mode that has been specified Default off Operating Mode Used to specify an operating mode to which the camera map will apply When the controller is in a different operating...

Page 29: ...t Off Unswitched Trunks Modifies the behaviour of the input trunks from a site so that different trunks will be used for different remote cameras assuming the remote camera number matches the trunk nu...

Page 30: ...is section allows a number of miscellaneous features to be enabled Modification of any of these values should be done with care Uncontrolled Telemetry If enabled telemetry is forwarded to the cameras...

Page 31: ...he site controller will automatically display a fixed camera input when an operator selects a camera that is barred to them The input selected is the last on Matrix 0 Default Off Legacy VCR MUX protoc...

Page 32: ...e Defines which ports a time date signal is broadcast on Default ZVM ZVK and Intersite Internal TDG The ZSC 1000 has it s own time source which can be used to synchronise the system If this box is tic...

Page 33: ...Camera o Field 2 Preset o Field 3 Site Walk Start a camera s mimic patrol o Field 1 Camera o Field 2 Mimic o Field 3 Site Patrol Start a camera s ordered patrol o Field 1 Camera o Field 2 Patrol o Fie...

Page 34: ...dual day of the week a combination of days or every day Default Every day Hour Select an hour for the event or hourly operation 0 23 to specify the hour 24 to trigger the event every hour Default 0 Mi...

Page 35: ...ault 0 Dwell The hold dwell time between positions in the sequence In the range 1 65534 in units of seconds Default 3 Static The definition of the components of a sequence position Camera Camera addre...

Page 36: ...fy that a monitor should only display alarms with a matching group number Enter group zero default to allow all alarms to display on a monitor regardless of their group Default 0 Alarm VCRs The list o...

Page 37: ...seconds Cancel time The time after an alarm source clears itself before it is automatically cancelled Default 20 seconds Postpone time The time that an alarm is postponed for before it is re reported...

Page 38: ...device generating the alarm depending on the type of the alarm Device 0 represents all devices of a particular type i e global mapping Default 0 Number The actual number of the alarm circuit on the a...

Page 39: ...formed on the selected camera No action Preset Walk Patrol Random Relay On Relay Off Relay Pulse Set Mode Default No action Note Relay Actions If the Primary Action Camera is on a remote site the rela...

Page 40: ...porting 101 127 Site 1 27 Default 99 Remote Site Report the alarm to a remote site specified in global alarm section Default Off Notes If no reporting is specified for all events assigned to an alarm...

Page 41: ...ite controller will either leave the current monitor selection or switch to a fixed input This behaviour is defined in the Enables section Note Camera barring does not apply to the highest priority le...

Page 42: ...1000 System Reset 1 The application has a number of check procedures built in and will automatically reboot if it detects an inconsistency in its data This will allow the unit to recover An active ope...

Page 43: ...by our staff along with the reported problem 3 Pack the ZSC 1000 into the original packing it was delivered in Failure to do so means the unit may incur further damage in transit which Meyertech cann...

Page 44: ...al requirements beyond safe working practice in the decommissioning of the Meyertech ZSC 1000 However the ZSC 1000 contains printed circuit boards populated with electronic components The whole unit m...

Page 45: ...information your require visit http www meyertech co uk support html Meyertech offer Extended Support Contracts on all their software products Please contact our Sales department on 0161 643 7956 to d...

Page 46: ...hall be entitled at its absolute discretion on return of the defective Goods to the Seller at the Seller s request to refund the price of the defective Goods in the event that such price shall already...

Reviews: