Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
53
Display
Description
Operating mode
Fire routing acknowledgement (type 2, 240 seconds)
[1] [3]
An active input indicates acknowledge after fire
routing is active. An active input in other condition
generates a fire routing fault.
EN 54-2
EN 54-2 Scandinavian
NEN 2535
FBF interface (sounders disabled) [2] [3]
Active input disables sounders and silences the
control panel.
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavian
NEN 2535
BS 5839-1
[1] May only be configured for one input per control panel.
[2] Regional fire brigade panels. May only be configured for one input per control panel.
[3] Supervision for wiring open and short conditions available. A 15
kΩ
end-of-line is required.