Chapter 3: Configuration and commissioning
44
ZP1-F Series Installation Manual
Display
Menu
Values
Operating mode
Fire routing delay
(or Warning sounder delay
for NBN S 21-100 mode)
00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Extended fire routing delay
00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NEN 2535
Add an expansion board [1] 00 to 04 modules
All
Fire network identifier [2]
00 to 32
All
Software version
Read-only
All
Configuration version
Read-only
All
Configuration time stamp
Read-only
All
Configuration date stamp
Read-only
All
Zone configuration [1]
Passive EOL
Active EOL
Unlatched
Passive EOL with CleanMe
Active EOL with CleanMe
Intrinsically-safe
All
Zone delay
ON/OFF
All
Zone type
Mixed
Automatic
Manual
All
Input configuration
Remote reset
Delays off
Fire routing extended delay
Fire routing inhibit delay
Class change
Fault warning output open
supervision (NEN 2535
only)
Fire routing
acknowledgement (type 1,
100 seconds)
Fire routing
acknowledgement (type 2,
240 seconds)
FBF interface (sounders
disabled)
All
Summary of Contents for ZP1-F2
Page 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Page 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Page 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Page 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Page 113: ......