Chapter 2: Installation
14
ZP1-F Series Installation Manual
Connecting supervised inputs
Connect supervised input switches to INPUT1 and INPUT2, as shown in Figure 8
below.
Figure 8: Connecting supervised inputs
Nominal resistance values (including any cable resistance) are shown in Table 8
below.
Table 8: Nominal resistance values for supervised inputs
Input function
Input
Value
[1]
State
Fire routing acknowledgement (type 1,
100 seconds)
1
≤ 220 Ω
Short circuit
> 220 Ω to 8 kΩ
Active [2]
> 8 kΩ to 10 kΩ
Fault [3]
> 10 k
Ω
to 20 kΩ
Standby
> 20 kΩ
Open circuit
[1] Values between each state may vary, depending on tolerance.
[2] For EN 54-13 compliance, the active impedance should be i
n the range of 220 Ω to 3.9 kΩ.
[3] High impedance fault.
Table 9: Nominal resistance values for “fault warning output” open supervision inputs
Input function
Standby
Fault (open)
Fault warning output: open circuit supervision
≤ 9 kΩ
> 9 kΩ
[1] For the open circuit supervision of the fault warning output with the input, a 2010-FS EOL
board must be installed. See “Connecting the fault warning output” on page 17.
Summary of Contents for ZP1-F2
Page 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Page 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Page 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Page 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Page 113: ......