Chapter 2: Installation
ZP1-F Series Installation Manual
15
Connecting supervised outputs
Control panels have the following supervised outputs:
• Two-zone control panels have two outputs, marked OUT1 and OUT2.
• Four- and eight-zone control panels have four outputs, marked OUT1, OUT2,
OUT3, and OUT4.
The outputs are supervised for open and short circuit faults.
Output class
The control panel outputs can be configured for Class A or Class B operation,
depending on the supervision mode required. The default output configuration is
Class B.
Table 10: Output classes and EN 54-13 supervision
Output class
EN 54-13 supervision
Description
Class B (default)
Disabled
For installations not requiring EN 54-13
compliance
Class A
Enabled
For installations requiring EN 54-13
compliance
For more information, see “EN 54-13 supervision mode” on page 36.
Output functionality
The function of each output is defined by the panel operating mode and output
class configuration (the default is Class B). All outputs are overload protected.
Table 11: Class B output functionality (default)
Operating mode
OUT1
OUT2
OUT3
OUT4
EN 54-2
Sounders
Sounders
Sounders
Fire routing
EN 54-2 Evacuation
Sounders
Sounders
Sounders
Sounders
EN 54-2 Scandinavia
Sounders
Sounders
Sounders
Fire routing
BS 5839-1
Sounders
Sounders
Sounders
Sounders
NBN S 21-100
Evacuation
sounders
Evacuation
sounders
Warning
sounders
Warning
sounders
NEN 2535
Sounders
Sounders
Fire routing
(automatic)
Fire routing
(manual)
Summary of Contents for ZP1-F2
Page 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Page 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Page 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Page 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Page 113: ......