Appendix A: Configuration presets
92
ZP1-F Series Installation Manual
EN 54-2 Scandinavia
Table 50: Configuration presets
Preset Control
panel
EOL type
Output
type
Sounder
outputs
Fire routing
outputs
Zone type
07
Two-zone
Passive
Class B
2
0
Mixed
07
Four-zone,
eight-zone
Passive
Class B
3
1
Mixed
08
Two-zone
Passive,
CleanMe
enabled [1]
Class B
2
0
Mixed
08
Four-zone,
eight-zone
Passive,
CleanMe
enabled [1]
Class B
3
1
Mixed
07
Two-zone
EN 54-13
supervision
Class A
1
0
Odd: Automatic
Even: Manual
07
Four-zone,
eight-zone
EN 54-13
supervision
Class A
1
1
Odd: Automatic
Even: Manual
[1] The CleanMe feature is not available for Ziton devices.
Table 51: Additional configuration characteristics
Default sounder delay
0
Default fire routing delay
1
Default extended fire routing delay
3
Default zone delay
0n
Start/Restart sounders
Start sounders or restart stopped sounders at Operator
user level with or without a fire alarm event
Table 52: Inputs and outputs
Input/Output
Standard
EN 54-13
INPUT1 (Two-zone control
panel)
Remote reset
Remote reset
INPUT1 (Four- and eight-zone
control panels)
Fire routing delay / extended fire
routing delay
Fire routing delay / extended
fire routing delay
INPUT2
Delays off
Delays off
OUT1
Sounder circuit
Sounder circuit
OUT2
Sounder circuit
OUT3
Sounder circuit
Fire routing
OUT4
Fire routing
Note: Two-zone control panels have only two outputs with EN 54-13 disabled (OUT1 and OUT2)
or a single output with EN 54-13 enabled (OUT1/2).
Summary of Contents for ZP1-F2
Page 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Page 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Page 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Page 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Page 113: ......