Chapter 3: Configuration and commissioning
52
ZP1-F Series Installation Manual
Input configuration
Use this menu to configure the functionality of INPUT1 and INPUT2. The default
setting for each input is included in Appendix A “Configuration presets” on page
89.
To configure an input:
1. Set the display as shown below, and then press Enter.
2. Select the input (for example, INPUT1), and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Operating mode
Remote reset.
Input activation (transition) commands reset.
All
Delays off
Input activation (transition) deactivates delays
(equivalent to night mode).
Input deactivation (transition) activates delays
(equivalent to day mode).
All
Extended fire routing delay
Input active configures extended fire routing delay.
EN 54-2
EN 54-2 Scandinavian
NEN 2535
Fire routing inhibit delay
Input active deactivates fire routing delays.
EN 54-2
EN 54-2 Scandinavian
NEN 2535
Class change
Sounders are activated while the input is active
All
Fault warning output open supervision
An inactive input indicates the fault warning output
has an open circuit wiring fault.
NEN 2535
Fire routing acknowledgement (type 1, 100 seconds)
[1] [3]
An active input indicates acknowledge after fire
routing is active. An active input in other condition
generates a fire routing fault.
EN 54-2
EN 54-2 Scandinavian
NEN 2535
Summary of Contents for ZP1-F2
Page 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Page 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Page 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Page 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Page 113: ......