Operation (short) MP 2.1
FC20xx Fire control panel
FT2040 Fire terminal
ALARM-Procedure Page
1
Switching off detector zones / detectors
Page 2
Switching on detector zones / detectors
Page 4
Procedure in case of Fault
Page 4
Document ID: 009906_d_en_GB
Edition: 05.2009
1 of 4
ALARM Procedure
with Alarm Verification Concept (AVC), suggested possible procedure, subject to local requirements
Action / Condition
Consequence / Status
1.
Press
<Acknowledge>
on the PMI before allowed
response time (t1) runs out (Password required)
Buzzer is turned off, alarm is acknowledged.
Countdown t2 for the investigation of the cause of alarm starts.
2.
Read
top line
on display:
"Fire brigade in" "mm:ss"
Remaining time is shown as countdown before building
evacuation and Fire Brigade call.
3.
Read fire location
on display.
4.
Go to the fire location.
Information on the cause of ALARM,
damage limitation.
5.
Decide
: MAJOR INCIDENT or minor incident.
If required, initiation of suitable emergency measures.
6.
MAJOR INCIDENT:
A
Press <
Alarm delay off
>
or actuate
nearest
manual call point.
Read top line
on display:
●
"Remote transmission activated"
●
"Fire brigade called !"
●
"Call fire brigade !"
Remote transmission switched off / not available or
defective.
The remote transmission for fire alarm is activated
immediately.
●
Transmission to fire brigade not confirmed yet.
●
ALARM transmitted to fire brigade.
●
Fire brigade must be called by phone!
No automatic transmission to fire brigade.
Dial the following no.:
Minor incident:
R
Press
<Reset>
.
(Password required)
Fire detection system is in normal condition unless another event
occurs.
It may be necessary to vent the room before resetting is possible.
Elements that cannot be reset can be switched off temporarily.
7.
During the alarm, optionally press
<Sounders Evacuate>
on the PMI.
(Password required)
Deactivates the acoustic alarm devices during the alarm.
(Reactivation is possible by pressing the button again)
1
2
3
4
5
6
7
8
9
*
0
#
C
ok
a
bc
~
gh
i
j
kl
m
no
pq
rs
tu
v
wx
yz
de
f
ALARM
FAULT
ISOLATION
DETECTOR TEST
System
On
Fault
Scroll alarms
Remote alarm
Active
Fault / Off
Sounders
Fault / Off
Active Evacuate
Silence buzzer
Acknowledge
Reset
Alarm delay off
Premises manned
Fire brigade in
001 ALARM
Autom. FIRE ALARM Zone no.2
Execute
Commands
More
Options
Fx20xx
Control function
Fault / Of
Active
7.
A
2.
1.
R
6.
5
.4.
Go to fire location
Decide
00:02:51
Switch to
Standard view
3.
Main Building
Ground Floor
1/01 Meeting Room 001
00:02:51