background image

 

Document ID: 009906_d_en_GB 

 

Edition: 05.2009

 

4 of 4 

 

 

Switching on detector zones / detectors

 

(Password required)

 

 

 

 When there is no event with a higher priority, isolations (switched off) are directly indicated on the display. You 

may then directly proceed with Step 3 below. 

 

 When all zones (a zone is a detector in this system’s terminology) are turned off, the section is additionally 

indicated as switched off.

 

 

 Detectors that still contain smoke or test gas cannot be switched back on.

 

 Step

 

 Result

 

1. 

Press the button 

 to open the main menu. 

(password required) 
Press 

<1>

 

"Message summary". 

 

Message summary 
Exit with <C> 

Access level 2.1

002 
003 
 

Isolations 
Information 

(4)
(8)

Function 

On/Off

 

Function 

All

 

LED 
Test

 

2. 

Press 

<4>

 

"Isolations".

 

2007-10-10  15:14:36 

002 Isolations 
OFF 
1/01 Reception 
OFF 
Ground Floor 

 

Zone no 2 
 
Zone no 2 

001

002

Execute 

command 

Switch to 

extended view 

More 

options

 

3. 

 Scroll with the navigation buttons to the 

isolation (detector e.g. Reception, or zone 
e.g.Ground Floor) you want to switch on.  
The selected isolation is marked by a frame. 
Press 

Softkey

 

<1>

 

"Execute command”.

 

 

 

Select command 
ON (1) 

 
 
 
 

4.

  Press 

<1>

 

"ON".

 

 

Command response confirms the execution. 

 

Detector or zone switched on. 

 

LED "ISOLATION" is off, provided that there is no other 

isolation. 

 

 

Procedure in case of Fault

 

 Step 

 

 Result

 

1. 

Press 

<Silence buzzer>

 on the PMI. 

Buzzer on the station switched off. 

2.

  Read 

message/fault location

 on the display. 

Information on type and place of the fault. 

3.

  Press 

<Acknowledge>

 on the PMI. 

 

 

4.

 

Go to the fault location and remedy the cause 
of the fault.

 

The fault will clear automatically from the station. 

 

If you cannot eliminate a fault, please contact your service provider.

 

 

Summary of Contents for FC20

Page 1: ...de called Call fire brigade Remote transmission switched off not available or defective The remote transmission for fire alarm is activated immediately Transmission to fire brigade not confirmed yet ALARM transmitted to fire brigade Fire brigade must be called by phone No automatic transmission to fire brigade Dial the following no Minor incident R Press Reset Password required Fire detection syst...

Page 2: ...Functions Exit with C Access level 2 1 On Off Test Activate deactivate Information 1 2 3 4 Configuration Maintenance All functions 5 6 7 Function On Off Function All LED Test 3 Press 1 On Off Select element category Zone Area Section Detector RT control 1 2 3 4 5 4 Press 3 Section Note A British Standard zone is called a Section in this system s Enter address Zone no Confirm with ok Exit with C De...

Page 3: ...el Execute commands 4 Press Softkey 2 Lower level Scroll with the navigation buttons to the section within which is the detector that you want to switch off The selected section is marked by a frame Note As an alternative to switching off a zone page 2 executing commands at this point will then lead to the menu item to switch a whole zone of detectors off 004 Items Area Main Building Second Floor ...

Page 4: ...007 10 10 15 14 36 002 Isolations OFF 1 01 Reception OFF Ground Floor Zone no 2 Zone no 2 001 002 Execute command Switch to extended view More options 3 Scroll with the navigation buttons to the isolation detector e g Reception or zone e g Ground Floor you want to switch on The selected isolation is marked by a frame Press Softkey 1 Execute command Select command ON 1 4 Press 1 ON Command response...

Page 5: ...on display 4 Go to fire location Information on the cause of ALARM if required initiate required emergency measures and damage limitation 5 In case of a minor incident R Press Reset Password required Fire detection system is in normal condition unless another event occurs It may be necessary to vent the room before resetting is possible Elements that cannot be reset can be switched off temporarily...

Page 6: ...ons Exit with C Access level 2 1 On Off Test Activate deactivate Information 1 2 3 4 Configuration Maintenance All functions 5 6 7 Function On Off Function All LED Test 3 Press 1 On Off Select element category Zone Area Section Detector RT control 1 2 3 4 5 4 Press 3 Section Note A British Standard zone is called a Section in this system s terminology Enter address Zone no Confirm with ok Exit wit...

Page 7: ...el Execute commands 4 Press Softkey 2 Lower level Scroll with the navigation buttons to the section within which is the detector that you want to switch off The selected section is marked by a frame Note As an alternative to switching off a zone page 2 executing commands at this point will then lead to the menu item to switch a whole zone of detectors off 004 Items Area Main Building Second Floor ...

Page 8: ... 15 14 36 002 Isolations OFF 1 01 Reception OFF Ground Floor Zone no 2 Zone no 2 001 002 Execute command Switch to extended view More options 3 Scroll with the navigation buttons to the isolation detector e g Reception or zone e g Ground Floor you want to switch on The selected isolation is marked by a frame Press Softkey 1 Execute command Select command ON 1 4 Press 1 ON Command response confirms...

Reviews: