28
Installation and operating instructions
5.5.2 Assembling the DC connectors
Assemble the DC connectors as described below. Be sure to observe the correct
polarity. The DC connectors are marked with the symbols "+" and " − ".
Cable requirements
:
The cable must be of type PV1-F, UL-ZKLA or USE2 and comply with the following
properties:
External diameter: 5-8 mm
Conductor cross-section: 2.5-6 mm²
Number of conductors: at least 7
Nominal voltage: at least 1000V
Proceed as follows to assemble each DC connector.
1
Strip 12 mm of the cable insulation.
2
Route the stripped cable all the way into the DC connector. Ensure that the
stripped cable and the DC connector have the same polarity.
3
Press the clamping bracket down until it audibly snaps into place.