50
Installation and operating instructions
NOTICE!
The safety of the grid may be influenced due to the wrong safety setting!
•The default parameters settings comply with the local regulations.
•Don’t change the values of the monitored operational limits unless the utility
provider agrees with your requirement!
9.4.11 Safety setting
Enter the sub-menu “Advanced Setting” and press the "
" button to input the
password.The password is required if you want to change some one parameters.
Please get the correct password from the service engineer. Enter the correct
password and "
" to enter the advanced setting page.
Then enter the sub-menu of “settings” and select the “Advanced setting” item and
confirm. The password page is now displayed.
Press the "
▲
"or "
▼
"button to modify the password digit, press the "
"button to
change the next digit, and the advanced page is now displayed lastly.
Password
Password:0 0 0 0
0
Overload Setting
Active power control
Reactive power control
PV Mode Setting
Advanced Setting
EEG Setting
Safety Setting
To modify parameters, use the "
▲
" or "
▼
" button to modify the selected parameter
and confirm with the "
" button. Then the next parameter will be selected.
Press the "ESC" button to cancel.
Safety
Standard:
DE VDE-AR-N 4105
OVP2
:
265.5 V
OVP1
:
255.0 V
UVP1
:
185.0 V
UVP2
:
180.0 V
10Min-Mean
:
180.5 V
Safety
OFP2
:
54.50 Hz
OFP1
:
UFP1
:
UFP2
:
53.50 Hz
47.50 Hz
45.50 Hz
There are two pages of safety parameters. After modifying the last parameter of
the first page, press "
"to switch to the second page.