Installation and operating instructions
23
3
Strip the cable jacket (72mm) and the insulation (8.5mm), cable size 10mm² Max.
Insert bared conductors into the cord end terminal and crimp the contact. The
cord end terminals provided are only suitable for stranded copper wire AWG 10.
4
Insert the stripped conductors L1, L2, L3, N and PE into the corresponding
terminals and tighten the screw with torque 2.0-2.5Nm using an Allen key
(
AF
3.0
)
. The ground wire must be locked in the “PE” position.
CAUTION!
The inverter can be destroyed due to the wrong wiring!
Please ensure that the polarity of the conductors matches the signs of the screw
terminals on the socket element.
5
Assemble the socket element, adapter and cable nut as shown below with a
torque of 3-4Nm.