INFORMATION
If need to use Y adaptors, please refer to the information below.
Y adaptors must not be visible or freely accessible in the immediate vicinity of
the inverter.
• The DC circuit must not be interrupted by Y adaptors.
• In order to interrupt the DC electric circuit, disconnect the inverter from all
voltage sources
5.5.1 Connection of the PV generator (DC)
• PV modules of the connected strings must be of:
– the same type
– the same number of series-connected PV modules
– identical alignment
– identical tilt
• The connection cables of the PV modules must be equipped with the connectors
included in the scope of delivery.
• At the DC input of the inverter, the following limits must not be exceeded:
*) The Max. open-circuit voltage, which can occur at PV modules temperature of -10
℃
,
must not exceed the Max. DC input voltage of the inverter.
• The positive connection cables of the PV modules must be equipped with the positive
DC connectors.
• The negative connection cables of the PV modules must be equipped with the
negative DC connectors.
• At an ambient temperature over 10
℃
, the open-circuit voltage of the PV strings must
not exceed 90% of the maximum DC input voltage of the inverter. This prevents the
voltage from exceeding the maximum DC input voltage of the inverter at lower
ambient temperatures.
Type
Max. DC voltage *
Max. DC current
Max. short-circuit current
TLC 10K
1000V
22 A/11 A
32.4 A/16.2 A
TLC 15K
1000V
22 A/22 A
32.4 A/32.4 A
TLC 17K
1000V
22 A/22 A
32.4 A/32.4 A
TLC 20K
1000V
22 A/22 A
32.4 A/32.4 A