56
Installation and operating instructions
Type
TLC 17K
TLC 20K
Rated DC input power (Pdc,r)
17600 W
20800 W
Max. recommended DC input power
at STC
(1)
19500 W
23000 W
Max. DC input voltage
1000 V
(2) (3)
Rated DC input voltage
640 V
MPP voltage range
270 … 950 V
Full load MPP voltage range
390 … 800 V
450 … 800 V
Start-up DC input voltage
300 V
Min feed-in DC voltage
270 V
Max. DC input current (input A/B)
22 A/ 22 A
Isc PV, absolute Max. (input A/B)
32.4 A/ 32.4 A
Number of MPP trackers
2
Strings per MPP tracker (input A/B)
2 / 2
Turn on power
25 W
DC-switch
Optional
(1)
For fixed systems with semi-optimal conditions.
(2)
When DC input Voltage is higher than 1000V, the inverter will alarm an error.
When DC input Voltage is below 950V, the inverter begins to check and connect
to gird.
(3)
The 1000V firmware release varies by region. For details please talk to your
local contact person.
Summary of Contents for Eversol-TLC 10K
Page 1: ......