Installation and operating instructions
67
Resumable
Fault
33
•Check the grid frequency and observe how often major fluctuations
occur.
If this fault is caused by frequent fluctuations, try to modify the
operating parameters after informing the utility provider first.
35
•Check the fuse and the triggering of the miniature circuit breaker in
the distribution box.
•Check grid voltage, grid usability.
•Check AC cable, grid connection on the inverter.
If this fault is still being shown, please call service.
34
•Check the grid voltage and grid connection on the inverter.
•Check the grid voltage at the point of connection of the inverter.
If the grid voltage is outside the permissible range due to local grid
conditions, try to modify the values of the monitored operational
limits after informing the electric utility company first.
40
•Check whether the airflow to the heat sink is obstructed.
•Check whether the ambient temperature around the inverter is too
high.
Permanent
Fault
1,2,3,4,
8,9,10,
11, 39
Disconnect the inverter from the grid and the PV generator,
reconnect them after 3 minutes. If this fault is still being shown,
please call service.