Installation and operating instructions
21
Cable design
The conductor cross-section should be dimensioned to avoid power loss in cables
exceeding 1% of rated output power.
The maximum cable lengths relative to the conductor cross-section as follows:
conductor
cross-section
Maximum cable length
TLC 10K
TLC 15K
TLC 17K
TLC 20K
6 mm²
48 m
32 m
28 m
24 m
10 mm²
70 m
53 m
47 m
40 m
The required conductor cross-section depends on the inverter rating, ambient
temperature, routing method, cable type, cable losses, valid installation
requirements of the country of installation, etc.