Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 26 of 44
14/12/06
2.
Remove the resistor from the Fire Protection output circuit terminal and
connect the field wiring to the terminals, observing correct polarity. Check that
any fault indications clear after a few seconds.
3.
Initiate a fire condition on a zone to operate the output. Check that the fire
signal operates the interface relay adjacent the fire protection equipment.
4.
Open-circuit the field wiring and confirm that the fire alarm panel indicates
Fire Protection output fault.
5.
Reconnect the cabling and confirm the faults clear.
6.
Final testing and commissioning of the loop through to the fire protection
equipment, including test [simulated] activation of the equipment, should be
carried out at the appropriate time in conjunction with the engineer responsible
for the fire protection system.
13.7.6
Commissioning ancillary inputs
Remote Silence Alarms, Reset and Evacuate inputs should each be tested by the
activation of the remote equipment. The response should be verified for each signal.
13.7.7
Commissioning ancillary outputs
The correct operation of equipment connected to the Zone Outputs, Disablement
Active, Evacuate Active and Buzzer Active outputs should be verified in turn by
initiating a fire condition on each of the appropriate zones; disabling/enabling a zone;
operating the Evacuate button on the panel’s display.
13.7.8
Commissioning repeaters
1.
Power-up the Panel and then the Repeaters. Only the “Power Supply On”
LEDs should be illuminated on the Panel and Repeaters.
2.
At Repeater 1, turn the Access control switch to “1”, and press the “Evacuate”
button. Check that the alarms operate and the internal buzzer operates on all
repeaters.
3.
Press the “Silence” button on the fire alarm panel. Check that the alarm
circuits silence and the internal buzzer silences on all repeaters.
4.
Repeat steps 2 and 3 for each repeater.
5.
Operate a Manual Call Point on zone 1 and check for correct fire indication at
each repeater.
6.
Press the “Silence Alarms” button on a repeater and check that the alarms are
silenced and the Zone 1 fire LED is constantly illuminated on all repeater
panels.
7.
Press the “Reset” button on a repeater and check that the panel and repeaters
return to the quiescent state.
8.
Repeat steps 5 to 7 for each zone and ensure “Silence Alarms” and “Reset”
operate correctly from each repeater.
9.
Set the DIL switches on the C1631 Repeater Interface card in the fire alarm
panel OFF (No Repeaters). Check that all repeaters indicate a “Comms. Fault”.
10.
Set the C1631 Repeater Interface card DIL switches in the fire alarm panel
back to their previous settings and check that the repeaters return to normal.