Premier MX C1632 16 zone expansion board Features
Figure 11 - C1632 16 zone expansion board
11.
Power Supplies
The Premier MX 2,4, 8 and 16 zone panels produce d.c. power regulation directly on
the C1627 motherboard. The Precept 32 zone panel has an off-board power supply via
a dedicated PCB (C1652) contained within the enclosure of the fire alarm panel.
For all panels, the output voltage is adjustable from 25V to 28.2V via a small trimmer
potentiometer on the PCB. As the output voltage is factory set however, this should
not be necessary.
11.1
Visual indications
The following visual indications are provided:
1)
A green
‘Output – OK’
LED. This simply denotes that power is being supplied to
the panel
2)
A yellow
‘Batt/Charge Fault’
LED denoting any one of the following conditions:
a)
Battery disconnected
b)
Battery fuse blown
c)
Low Battery voltage
3)
A yellow
‘Charger Fault’
LED. This denotes that the switching regulator has
stopped working and could be due to the following reasons:
Connector for
motherboard
ribbon
Detection zone
terminals for
zones 17 – 32