Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 25 of 44
14/12/06
•
Continue to check the operation of all other manual call points on the
zone, resetting the manual call point and silencing/resetting the panel at
each stage.
•
Refit the detector and check that the control panel returns to its normal
state.
•
Continue to test each of the other detectors in turn, checking on each
removal that:
The appropriate amber zone fault LED illuminates
The internal buzzer sounds.
The fault relay operates.
5.
Repeat steps 1 to 4, one zone at a time, until all the zones are commissioned.
6.
Any faults that are found must be traced and rectified before proceeding.
13.7.3
Commissioning the Class Change Input
1.
Connect the Class Change switch to the class change input on the
motherboard.
2.
Operate the class change switch and observe:
i)
The alarms sound for 5 seconds then stop.
ii)
The internal buzzer on the panel
does not
operate.
iii)
The internal buzzer on repeaters
does not
operate.
3.
De-activate the class change switch
13.7.4
Commissioning the Fire and Fault Routing Outputs
1.
Remove the resistor from the Fire Routing output circuit terminals and connect
the field wiring to the terminals, observing correct polarity. Check that any
fault indications clear after a few seconds.
2.
To operate the output, initiate a fire condition on a zone. Check that the fire
signal is received at the receiving station. Silence and reset the fire alarm panel
to clear the output.
3.
Remove the resistor from the Fault Routing output circuit terminals and
connect the field wiring to the terminals, observing correct polarity. Check that
any fault indications clear after a few seconds.
4.
Initiate a fault condition on the fire alarm panel to signal a fault to the remote
receiving station.
5.
Confirm the receipt of the fault warning at the receiving station.
6.
Open-circuit the output wiring of each circuit in turn, confirm the fire alarm
panel indicates Fire Routing and Fault Routing faults appropriately.
7.
Reconnect the cabling and confirm the faults clear.
13.7.5
Commissioning the Fire Protection control signal
1.
Ensure any fire protection equipment to be controlled via the Fire Protection
output is locked off/safe before attempting any connection, testing or
commissioning.