To configure the Fault Routing Output to volt-free relay contacts, remove links J6, J7
and J8. [These links are combined in a single block].
These links are located below the associated output in the top right hand section of the
C1627 motherboard. See Figure 10 – C1627 Premier MX motherboard layout
15.9
Disabling the earth fault monitoring
To disable the earth fault monitoring, remove the link J18 located towards the bottom
right hand corner of the C1627 motherboard. See Figure 10 – C1627 Premier MX
motherboard layout.
16.
Optional Clock Module - configuration and setting
16.1
Standard Module Engineer Mode:
16.1.1
To zero the alarm counter:
Open panel door and move the DIL switch 1, pole 2 on clock
module PCB to the ON position. Return
the DIL switch to the
OFF position.
16.1.2
To access the Engineer’s Clock Module Edit Functions
Normal Time Display:
HH:MM:SS
or
HH:MM:SS
D/N ON
D/N OFF
Select Access Control key switch to position 1.
Press the SELECT ON/OFF switch.
Use the “Up/down” keys to scroll the cursor LED indication
through the selectable options on the display LEDs until LCD
backlight illuminates.
Normal Time Display:
HH:MM:SS
or
HH:MM:SS
D/N ON
D/N OFF
•
To change the Day/Night Mode
Press SELECT ON/OFF.
Delay On/Off Set Display:
D/N ON
or
D/N OFF
Change?
Change?
On the rear of the Clock Module PCB, move the DIL switch 1,
pole 1 on to the ON position.