Operating the Engineer’s functions
15.1
Engineer’s Zone/Output Configuration Process:
•
Various programmable configuration options associated with the zonal
inputs and outputs can be enabled/disabled by operating the appropriate
DIL switch located within the panel enclosure. These are:
o
Configure zones as delayed zones.
o
Configure zones for use with I.S. barriers/isolators.
o
Configure zones as latching/non-latching fire indication.
o
Configure zones to short circuit fire mode.
o
Configure outputs to be delayed.
Note: Configure Machinery Space Zones feature is not used on the standard
Precept
en
panels.
15.2
Zone or Output Configuration
•
1. Select a programmable configuration mode:
o
Enable the controls on the display, by turning the Access keyswitch on
the panel display to the “1” position.
o
If the panel is in the fire alarm condition, silence the alarms and reset.
o
Open the panel door and locate the appropriate DIL switch on the
motherboard [
Config Non-latch Zones; Config I.S. Zones; Config
Delay Zones; Config Delay O/Ps
] and move the switch actuator to the
ON position.
The
CONFIG ENABLED
LED on the motherboard will
illuminate.
The Panel’s
System Fault
LED will flash and the buzzer
will operate.
The Select LED on the front of the display will pulse.
Any standing fire or fault alarm indications and associated
outputs will be inhibited.
If active, the indications for evacuation, silence buzzer,
delay on or disablement indications will clear.
The panel will indicate the current status of the selected
programmable configuration mode on the yellow
fault/disabled
LEDs on the Zones, Sounders, Fire Routing
and Fire Protection outputs.
A steady indication denotes that the zone/output is already
configured to the selected mode.
No indication denotes that the zone/output has not been
configured to the selected mode.
o
Close the panel door to allow access to the buttons on the display.
•
2. Select a zone or output to be configured:
o
On the panel display, press the Select On/Off switch to enable the
Select Mode.
The Select LED will become steady and the panel buzzer
will silence.