Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 34 of 44
14/12/06
o
ON: Enables selected zones to be configured to Delay Mode via the
Engineer’s Select feature.
•
SW 1/8 - Configure Delay O/Ps:
o
OFF: Configuration mode disabled.
o
ON: Enables the selection of outputs, via the Engineer’s Select feature,
to which the panel delay will apply.
•
SW 1/9 - 2 Stage Delay:
o
OFF: Single Stage Delay Mode.
o
ON: Two Stage Delay Mode.
•
SW 1/10 - Alarms on Evac Only:
o
OFF: Sounders operate on any fire condition including evacuate.
o
ON: Selects sounders to operate only when the panel is in the evacuate
condition
o
Not EN54 complaint function. Provided to meet existing customer
requirements.
•
SW 2/1 - Silence Before Reset:
Select type of reset mode. [Not EN54 compliant function. Provided to
meet existing customer requirements]:
o
OFF: Reset available when panel is in the [un-silenced] fire or fault
condition.
o
ON: Fire Condition Reset available only when panel is in Alarm
Silenced condition. Fault reset available when panel is in the fault
condition.
•
SW 2/2 to 2/5 - Delay/Minutes:
Sets the duration of the variable time delay element [i.e. the single stage delay and
stage 2 of the two stage delay] in steps of 1 minute within the range 0-9 minutes. See
Table 1 - Motherboard Delay Switch Settings