Touch-MyDesign Plus
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com/
31
the step orders will be conditioned to this status, to prevent sending ineffective
requests.
The parameters for this function are:
Action
: defines the order type that the button will send once a short or long
press is performed (“Toggle”, “Off/Decrease” or “On/Increase”).
Dimming Step
: defines the dimming step (“100%”, “50%”, “25%”, “12%”, “6%”,
“3%” or “1%”) to be sent (through “
[Xn] Light Dimming
(Toggle/Increase/Decrease)
”) to the light dimmer with every long press.
Note
:
since dimmers typically do not apply the new light level immediately (i.e.,
the step is performed progressively) and since Touch-MyDesign Plus sends an
order to interrupt the step dimming once the user releases the button, it is
advisable to configure a step of 100%. This way, the user can perform any
dimming step by simply leaving the button pressed and then releasing it, without
needing to make successive button presses
.
LED Illumination Control
: analogous to the homonymous parameter for all the
above functions (see previous pages). The options in this case are “Regular”,
“State-Dependent” and “Dedicated Object”.
Shutter
Figure 23
Individual Button - Shutter.
The move up/down orders will be sent through the “
[Xn] Move Shutter (Toggle
Direction)
”, “
[Xn] Move Shutter Up
” or “
[Xn] Move Shutter Down
” one-bit objects
(depending on the selected action: “Toggle”, “Up” or “Down”, respectively), while the
step up/down orders will be through the “
[Xn] Stop Shutter / Step
”, “
[Xn] Stop