Touch-MyDesign Plus
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com/
20
Action on Long Press
: sets the value that will be sent through “
[X] Two
Objects: Long Press
” after the user long-presses one of the two buttons.
“Left: 0; Right: 1” (or “Down: 0; Up: 1” under a horizontally-oriented
configuration.
“Left: 1; Right: 0” (or “Down: 1; Up: 0” under a horizontally-oriented
configuration.
Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Button Pair Action (see section 2.1).
Long Press Threshold Time
: sets the minimum time the user should hold the
button in order to consider it a long press. The available range is 4 to 50 tenths
of a second, being 6 tenths the default value.
LED Illumination Control
: analogous to the homonymous parameter for the
Switch and Dimmer functions (see above). In this case, however, selecting
“State-dependent” or “State-dependent (both LEDs)” brings an additional
parameter, “
LED Illumination State Object
”, to make the state of the LEDs
correspond either to object “
[X] Two Objects: Short Press
” (“Short Press
Object”) or to object “
[X] Two Objects: Long Press
” (“Long Press Object”).
Figure 14
Pair Buttons - Two Objects (Short Press / Long Press) - LED Illumination Control.
2.2.1.3
INDIVIDUAL
Buttons of pairs configured to work as individual (separate) controls can be assigned
any of the following control functions:
Disabled
: user presses will not trigger any function although the LED will still
react to them, if configured.
Binary
: whenever the user touches the button, a binary value will be sent to the
KNX bus. This value is configurable and may be 0 or 1, or alternate with every
touch according to the sequence 1
0
1
…